Capacitor cumhachd àrd bholtachd BAM
Iarrtas agus Inbhean:
Tha capacitor bholtachd àrd air a chleachdadh sa mhòr-chuid anns an t-siostam AC Power le 50Hz gus factar cumhachd a leasachadh. Tha an coileanadh a’ nochdadh gu GB 3083.2-89 《High bholtaids shunt capacitor》 agus IEC60871-1987.
GB/T11024-2010 Inbhe nàiseanta 《Boltaids ìre 1kV no nas àirde na capacitors shunt airson siostaman cumhachd AC
JB / 7112-2000 Inbhe gnìomhachas innealan 《HV Shunt Capacitor cruinnichte
DL/T628-1997 Inbhe Gnìomhachas Cumhachd Dealain 《Riatanas Teicnigeach òrdachadh HV Shunt Capacitor ag òrdachadh》
Riatanasan cleachdaidh:
1.Altitude: nas lugha na 1000m; Ambient Teòthachd: -40 ℃ ~ +40 ℃.
2. Gun chrathadh meacanaigeach fòirneartach, gun ghas is bhalbhaichean cronail, gun dealan, agus spreadhadh, agus duslach spreadhaidh san àite.
3.Continuous obrachadh bholtaids: 1.00 Un, fad-ùine max, Thar bholtaids: less.1 Un.
4.Stable over-curent (a 'gabhail a-steach gnàthach harmonics) nas lugha 1.3 In.
5.With seasamh bholtaids: eadar terminal 2.15, bholtaids ìre ùine airson 10 diogan, eadar cinn-uidhe agus container 42kV airson 10 diogan.
Prìomh fheartan teicnigeach:
1.Rated bholtaids: 6.3kV, 6.6kV, 6.6/√3kV, 7.96kV, 10.5kV, 11kV, 11kV, 11 / √3kV, feuch an cuir thu fios san òrdugh ma tha thu ag iarraidh an comas sònraichte eile.
2.Rated comas: 33 ~ 334kvar cuir an cèill san òrdugh ma tha thu ag iarraidh an comas sònraichte eile.
3.Capacity tolerance: -5 ~ 15%.
4.Loss aingeal luach buailteach: film & pàipear meadhanach tg θ≦0.08%, film meadhan tg θ≦0.05%.
5.Withstand bholtaids: faodaidh e cothrom a thoirt do AC2.15 no DC4.3 amannan bholtaids rangachadh eadar na pales comas, mu dheireadh mu 10sg gun bhriseadh no flash, BIL: 6kV(30kV), 10kV(42Kv).
Sgaoileadh 6.Free: tha an aghaidh a-staigh aige, 10min às deidh an solar cumhachd a ghearradh dheth, lughdaichidh am bholtadh fuigheall gu 75V bho √2 Un.
7.Max. An-dràsta: a 'ruith gu rèidh fon bholtadh ìre 1.3 ùine, thar bholtaids, comas fulangas dearbhach agus tonn harmonic nach urrainn a bhith nas fhaide na 1 min gach 24 uair.
8.Max.Current: a 'ruith gu rèidh fon bholtaids ìre 1.3 ùine, thar bholtaids, comas fulangas dearbhach agus tonn harmonic nach urrainn sruth 1.43 ùine a mheasadh.
9.Standard: GB/T 112024.1-2001, IEC6087:1997.
CAPACITOR CUMHACHD EILEANACH ÌRE
Modail BAM | Ìre Voltage (kV) | Toradh Rangaichte (kVAr) | Ìre comas (uF) | Ìre gnàthaichte ann an(A) |
6.3-25-1W | 6.3 | 25 | 2.006 | 3. 968 |
6.3-30-1W | 6.3 | 30 | 2.406 | 4.762 |
6.6 / √3-25-1W | 6.6/√3 | 25 | 5.481 | 6.561 |
6.3/√3-30-1W | 6.6/√3 | 30 | 6.577 | 7.873 |
6.3/√3-50-1W | 6.6/√3 | 50 | 10.96 | 13.12 |
10.5-25-1W | 10.5 | 25 | 0.722 | 2.38 |
10.5-30-1W | 10.5 | 30 | 0.886 | 2.857 |
10.5-50-1W | 10.5 | 50 | 1.444 | 4.762 |
11/√3-30-1W | 11/√3 | 30 | 2. 368 | 4.724 |
11/√3-50-1W | 11/√3 | 50 | 3. 946 | 7.873 |
6.3-30-1W | 6.3 | 30 | 2.4 | 4.76 |
6.3-50-1W | 6.3 | 50 | 4 | 7.9 |
6.3-100-1W | 6.3 | 100 | 8 | 15.9 |
6.3-200-1W | 6.3 | 200 | 16 | 31.7 |
6.3-300-1W | 6.3 | 300 | fichead 's a ceithir | 47.6 |
6.3-334-1W | 6.3 | 334 | 26.8 | 53 |
10.5-50-1W | 10.5 | 50 | 1.44 | 4.8 |
10.5-100-1W | 10.5 | 100 | 2.9 | 9.5 |
10.5-150-1W | 10.5 | 150 | 4.3 | 14.3 |
10.5-200-1W | 10.5 | 200 | 5.8 | 19 |
10.5-300-1W | 10.5 | 300 | 8.67 | 28.6 |
10.5-334-1W | 10.5 | 334 | 9.65 | 31.8 |
11/√3-50-1W | 11/√3 | 50 | 3.95 | 7.87 |
11/√3-100-1W | 11/√3 | 100 | 7.89 | 15.75 |
11/√3-150-1W | 11/√3 | 150 | 11.84 | 23.6 |
11/√3-200-1W | 11/√3 | 200 | 15.78 | 31.5 |
11/√3-300-1W | 11/√3 | 300 | 23.68 | 47.2 |
11/√3-334-1W | 11/√3 | 334 | 26.36 | 52.6 |
6.6 / √3-50-1W | 6.6/√3 | 50 | 10.96 | 13.12 |
6.6 / √3-100-1W | 6.6/√3 | 100 | 21.9 | 26.24 |
6.6 / √3-150-1W | 6.6/√3 | 150 | 32.9 | 39.36 |
6.6 / √3-200-1W | 6.6/√3 | 200 | 43.8 | 52.48 |
6.6 / √3-300-1W | 6.6/√3 | 300 | 65.8 | 78.7 |
6.6 / √3-334-1W | 6.6/√3 | 334 | 73.2 | 87.6 |
11-100-1W | 11 | 100 | 2.63 | 9.1 |
11-150-1W | 11 | 150 | 3.95 | 13.6 |
11-200-1W | 11 | 200 | 5.26 | 18.2 |
11-300-1W | 11 | 300 | 7.89 | 27.3 |
11-334-1W | 11 | 334 | 8.79 | 30.4 |
12-100-1W | 12 | 100 | 2.2 | 8.33 |
12-150-1W | 12 | 150 | 3.3 | 12.5 |
12-200-1W | 12 | 200 | 4.4 | 16.7 |
12-300-1W | 12 | 300 | 6.64 | 25 |
12-334-1W | 12 | 334 | 7.39 | 27.8 |
12/√3-100-1W | 12/√3 | 100 | 6.63 | 14.4 |
12/√3-150-1W | 12/√3 | 150 | 9.95 | 21.7 |
12/√3-200-1W | 12/√3 | 200 | 13.3 | 28.9 |
12/√3-300-1W | 12/√3 | 300 | 19.9 | 43.3 |
12/√3-334-1W | 12/√3 | 334 | 22.1 | 48.2 |
12/√3-400-1W | 12/√3 | 400 | 26.54 | 57.74 |
6.3-100-1W | 6.3 | 100 | 8 | 15.9 |
6.3-150-1W | 6.3 | 150 | 12 | 23.8 |
6.3-200-1W | 6.3 | 200 | 16 | 31.7 |
6.3-300-1W | 6.3 | 300 | fichead 's a ceithir | 47.6 |
6.3-334-1W | 6.3 | 334 | 26.8 | 53 |
6.6-100-1W | 6.6 | 100 | 7.3 | 15.2 |
6.6-150-1W | 6.6 | 150 | 11 | 22.7 |
6.6-200-1W | 6.6 | 200 | 14.6 | 30.3 |
6.6-300-1W | 6.6 | 300 | fichead 's a dhà | 45.5 |
6.6-334-1W | 6.6 | 334 | 24.4 | 50.6 |
6.6 / √3-100-1W | 6.6/√3 | 100 | 21.9 | 26.24 |
6.6 / √3-150-1W | 6.6/√3 | 150 | 32.9 | 39.36 |
6.6 / √3-200-1W | 6.6/√3 | 200 | 43.8 | 52.48 |
6.6 / √3-300-1W | 6.6/√3 | 300 | 65.8 | 78.7 |
6.6 / √3-334-1W | 6.6/√3 | 334 | 73.2 | 87.6 |
11/√3-100-1W | 11/√3 | 100 | 7.89 | 15.75 |
11/√3-150-1W | 11/√3 | 150 | 11.84 | 23.6 |
11/√3-200-1W | 11/√3 | 200 | 15.78 | 31.5 |
11/√3-300-1W | 11/√3 | 300 | 23.68 | 47.2 |
11/√3-334-1W | 11/√3 | 334 | 26.36 | 52.6 |
11-100-1W | 11 | 100 | 2.63 | 5.25 |
11-150-1W | 11 | 150 | 3.95 | 7.87 |
11-200-1W | 11 | 200 | 5.26 | 10.5 |
11-300-1W | 11 | 300 | 7.9 | 15.75 |
11-100-1W | 11 | 100 | 2.63 | 5.25 |
11-150-1W | 11 | 150 | 3.95 | 7.87 |
11-200-1W | 11 | 200 | 5.26 | 10.5 |
11-300-1W | 11 | 300 | 7.9 | 15.75 |
12-100-1W | 12 | 100 | 2.2 | 4.8 |
12-150-1W | 12 | 150 | 3.3 | 7.2 |
12-200-1W | 12 | 200 | 4.4 | 9.6 |
12-300-1W | 12 | 300 | 6.64 | 14.45 |
12-100-1W | 12 | 100 | 2.2 | 4.8 |
12-150-1W | 12 | 150 | 3.2 | 7.2 |
12-200-1W | 12 | 200 | 4.4 | 9.6 |
12-300-1W | 12 | 300 | 6.64 | 14.45 |
11/√3-200-1W | 11/√3 | 200 | 15.78 | 31.5 |
11/√3-334-1W | 11/√3 | 334 | 26.36 | 52.6 |
12/√3-200-1W | 12/√3 | 200 | 13.3 | 28.9 |
12/√3-334-1W | 12/√3 | 334 | 22.1 | 48.2 |
12-200-1W | 12 | 200 | 4.4 | 16.7 |
12-334-1W | 12 | 334 | 7.39 | 27.8 |
10.5-200-1W | 10.5 | 200 | 5.8 | 19 |
10.5-334-1W | 10.5 | 334 | 9.65 | 31.8 |